Skip to main content

Article 690.47: Grounding Electrode System












This Article is extracted from Mike Holt’s Illustrated Guide to Understanding NEC® Requirements for Solar Photovoltaic Systems.



Understanding NEC Requirements for Solar Photovoltaic Systems, Based on the 2011 NEC


Click here to buy a copy or read more about it.   



  





*Please note in the follwing extraction that blue underlined text indicates a 2014 NEC change.





Section 690.47 – Grounding Electrode System

(A) Alternating-Current PV System Grounding Requirements. For ac PV systems, a grounding electrode system must be provided in accordance with 250.50 through 250.60, with the ac grounding electrode conductor installed in accordance with 250.64.Figure 690–109

Im,age


Figure 690–109

(B) Direct-Current PV System Grounding Requirements. For dc PV systems, a grounding electrode system in accordance with 250.166 for grounded systems, or 250.169 for ungrounded systems, must be provided. Figure 690–110

Image3

Figure 690–110

A common dc grounding-electrode conductor can service multiple inverters. Section 250.166 is used to size the common grounding electrode and the tap conductors. The tap conductors must be connected to the common grounding-electrode conductor by exothermic welding or with connectors listed as grounding and bonding equipment.

The ac grounding electrode system can be used for equipment grounding of inverters and for the ground-fault detection reference for un-grounded PV systems.

(C) PV Grounded System with Alternating-Current Power System. Grounded PV systems constructed of dc modules must have the dc system grounded by one of the following methods:

(1) Separate dc Electrode. A grounding electrode conductor run from the marked dc GEC point at the inverter to the separate dc grounding electrode sized no smaller than the largest ungrounded dc conductor, but no smaller than 8 AWG [250.166(B)]. The dc grounding electrode must be bonded to the ac grounding electrode with a bonding jumper sized to the larger of the dc grounding electrode conductor [250.166] or ac grounding electrode conductor [250.66]. Figure 690–111

Image4

Figure 690–111

(2) Alternating-Current Grounding Electrode. A grounding electrode conductor sized in accordance with 250.166 must be run from the marked dc GEC point at the inverter to the ac grounding electrode. Figure 690–112

Image3

Figure 690–112

Where an ac grounding electrode isn’t accessible, the dc grounding electrode conductor must terminate to the ac grounding electrode conductor with a connector listed as grounding and bonding equipment. 690–113

Image2

Figure 690–113

(3) Combination ac Equipment Grounding Conductor/dc Grounding Electrode Conductor. For grounded PV Systems, the ac equipment grounding conductor sized to the larger of 250.122 or 250.166 can serve as both the ac circuit equipment grounding conductor and dc grounding electrode conductor. Figure 690–114

Image3

Figure 690–114

Author’s Comment:
  •  The ac equipment grounding conductor is sized in accordance with 250.122 based on the rating of the ac circuit overcurrent protection device; the dc grounding electrode conductor is sized no smaller than 8 AWG and no smaller than the dc circuit conductors [250.166(B)].

Question: What size EGC/GEC is required for a grounded PV system, where the inverter dc input circuit conductors are 14 AWG and the inverter ac output circuit conductors are 10 AWG protected by a 30A breaker? Figure 690–115

Answer: Table 250.122 requires the ac EGC to be sized no smaller than 10 AWG, and 250.166(B) requires the dc grounding electrode conductor to be no smaller than the largest dc circuit conductors, but no smaller than 8 AWG. In this case, the combined EGC/GEC must be no smaller than 8 AWG.
Image3

Figure 690–115

For ungrounded systems, the ac equipment grounding conductor sized no smaller than required by 250.122 based on the rating of the ac circuit overcurrent protection device can serve as both the ac circuit equipment grounding conductor and dc grounding electrode conductor.Figure 690–116

Image3

Figure 690–116

(D) Auxiliary Electrode for Array. A dc grounding electrode conductor from the array structure sized in accordance with 250.166 must be connected to a grounding electrode that complies with 250.52 and 250.54.

The metal structure of a ground- or pole-mounted PV array can serve as the grounding electrode if it complies with 250.52.

Roof-mounted PV arrays can use the metal frame of a building or structure as the electrode if it meets 250.52(A)(2). Figure 690–117

Image3

Figure 690–117

Ex No. 1: An array grounding electrode(s) isn’t required where the load served by the array is integral with the array.
Ex No. 2: An additional array grounding electrode(s) isn’t required if located within 6 ft of the premises wiring electrode.
Author’s Comment:
  • Auxiliary electrodes have no NEC requirements since they serve no useful purpose relating to electrical safety, yet are permitted. If an auxiliary electrode is installed, it isn’t required to be bonded to the building grounding electrode system, required to have the grounding conductor sized to 250.66, or to comply with the 25-ohm requirement of 250.53(A)(2) Ex [250.54].

CAUTION: An auxiliary electrode typically serves no useful purpose, and in some cases it may actually cause equipment failures by providing a path for lightning to travel through electronic equipment. Figure 690–118

Image3

Figure 690–118

2014 Change Analysis: The requirements for grounding the PV array were included in the 2008 Code, but disappeared in the 2011 edition. Due to the fact that there was no technical substantiation in either the report on proposals or the report on comments to remove it from the 2011 edition, it was inserted back into the 2014 Code without substantiation.


This Article is extracted from Mike Holt’s Illustrated Guide to Understanding NEC® Requirements for Solar Photovoltaic Systems based on the 2014 NEC®. 



Understanding NEC Requirements for Solar Photovoltaic Systems, Based on the 2011 NEC

Comments

Popular posts from this blog

States Electrical License Information

State of Oklahoma- Open the State of Oklahoma Electrical, Mechanical, Roofing, and Plumbing Examinations Candidate Information Bulletin Before paying for your examination registration, be sure you understand the contents of this bulletin. Please retain and use it as a reference when contacting PSI. Visit the State of Oklahoma Construction Industries Board View Rules/Laws Forms/ Applications Bond and Insurance CEU Courses Testing Information   _____________________________________ State of Utah- Open the State of Utah Division of Occupational and Professional Licensing Electrical Examinations Candidate Information Bulletin Before paying for your examination registration, be sure you understand the contents of this bulletin.  Please retain and use it as a reference when contacting PSI. Visit the State of Utah Division of Occupational and Professional Licensing View Statues and Rules Applications and Forms Board Information Continuing E

Texas Testing Centers-Addresses

The Texas Electrical Exam is conducted at the following test centers: City/State Address Driving Directions Abilene, Texas 1290 S Willis STE 109, The test site is on the corner of South 14th Street and Willis. The site is behind the First Financial Bank. Amarillo, Texas 4312 Teckla, Suite 500 From I-27 S, take exit 120B toward 45th Ave, and merge onto Canyon Dr. Turn right onto SW 45th Ave. Turn right onto Teckla. From I-27 N, take exit 119 toward Hillside Rd/ Western St. Merge onto Canyon Dr. Turn slight left onto S. Western St. Turn left onto Paramount Blvd. From I-40, turn onto S Western St. Turn right onto Paramount Blvd. Austin, Texas 8000 Anderson Square, Suite 301B If Northbound on Hwy 183 -take the Peyton Gin/Ohlen Road exit and stay in the left hand lane so you can turn left onto Anderson Square. Turn right into 8000 Anderson Square and immediately turn left, then right at the first chance. 301B is the end building on your right. If Southbo